A very quick article for Tuesday morning referring back to three Market Notices from AEMO yesterday.
At 19:08, the AEMO published MN117321 as follows:
‘——————————————————————-
MARKET NOTICE
——————————————————————-
From : AEMO
To : NEMITWEB1
Creation Date : 08/07/2024 19:08:46
——————————————————————-
Notice ID : 117321
Notice Type ID : LOAD SHED
Notice Type Description : NEL 116 Direction
Issue Date : 08/07/2024
External Reference : Load Shedding Direction in the NSW Region
——————————————————————-
Reason :
AEMO ELECTRICITY MARKET NOTICE
Load Shedding Direction in the NSW Region
AEMO has directed load shedding commencing at 1817 hrs 08/07/2024 in the NSW region to maintain power system security.
The direction was issued under section 116 of the NEL, and was a clause 4.8.9 instruction under the NER.
Manager NEM Real Time Operations
——————————————————————-
END OF REPORT
——————————————————————-‘
… but note no further details provided about specifically why they needed load shedding?
At 19:34 the AEMO published MN117322 as follows:
‘——————————————————————-
MARKET NOTICE
——————————————————————-
From : AEMO
To : NEMITWEB1
Creation Date : 08/07/2024 19:34:37
——————————————————————-
Notice ID : 117322
Notice Type ID : LOAD RESTORE
Notice Type Description : NEL 116 Direction
Issue Date : 08/07/2024
External Reference : Load Restoration Direction in the NSW Region
——————————————————————-
Reason :
AEMO ELECTRICITY MARKET NOTICE
Load Restoration Direction in the NSW Region
AEMO has directed load restoration commencing at 1930 hrs 08/07/2024 in the NSW region
The direction was issued under section 116 of the NEL, and was a clause 4.8.9 instruction under the NER.
Manager NEM Real Time Operations
——————————————————————-
END OF REPORT
——————————————————————-‘
Finally, at 21:58 the AEMO published MN117324 as follows:
‘——————————————————————-
MARKET NOTICE
——————————————————————-
From : AEMO
To : NEMITWEB1
Creation Date : 08/07/2024 21:58:40
——————————————————————-
Notice ID : 117324
Notice Type ID : LOAD RESTORE
Notice Type Description : NEL 116 Direction
Issue Date : 08/07/2024
External Reference : Cancellation – Load Restoration Direction in the NSW Region – 08/07/2024
——————————————————————-
Reason :
AEMO ELECTRICITY MARKET NOTICE
Cancellation – Load Restoration Direction in the NSW Region – 08/07/2024
Refer to AEMO Electricity Market Notice 117322
Load restoration as directed is complete. Direction cancelled from 2200 hrs 08/07/2024
Manager NEM Real Time Operations
——————————————————————-
END OF REPORT
——————————————————————-’
Nothing further at this point … but we are curious as to the why it was required?
PS1 … further information from AEMO
Apologies for the delay in adding in here … our friends at the AEMO have informed us of several things – including:
1) Monday night’s load shedding was in northern NSW to manage an unplanned network outage
(a) exactly which outage it was we don’t know for sure, at this point (though we have seen speculation elsewhere)
(b) for instance there was the ‘unplanned outage of all 3 cables of Directlink’ ... which was:
i. communicated in MN117323 at 19:41:53 (i.e. ~90 minutes after the direction for Load Shedding was given); and also
ii. reflected inside NEMDE by the ‘N-X_MBTE_3’ constraint set from the 18:45 dispatch interval (but noting that load shedding was directed from 18:17, so 28 minutes beforehand).
2) We understand that this is viewed as a ‘Reviewable Operating Incident’ under NER 4.8.15(a)(1)(v).
… as such, a preliminary report will be released next week.
PS2 … further information from others
There have also been updates from other sources, as well. For instance:
1) In Tom MacDonald’s comment below, he references three different unplanned network outages in NSW, and speculates possible contributions. We’ll need to wait for further information from AEMO to really know.
2) In Alex Cowie’s comment below, he points to this RenewEconomy article ‘Load shedding in NSW holiday spot after multiple transmission line trips’ which includes the following additional information:
‘Around 24,000 customers in northern NSW around Byron Bay went without power for more than an hour on Monday night after one of the main transmission lines tripped, causing the market operator to call for load shedding to keep the network stable.
A spokesman for the Australian Energy Market Operator said Transgrid’s 330 kV Lismore to Coffs Harbour line tripped earlier in the day, and load shedding was needed to secure network from soon after 6pm.
Essential Energy had to cut off power for about 24,000 customers in the area around Byron Bay, Lismore and Ballina after AEMO instructed Transgrid to shed a total of 40 megawatts of load.’
etc…
3) There are also other comments on this LinkedIn update that was triggered when our article was first published.
i. Amongst those comments is a link to the news article ‘Northern Rivers blacked out as Essential Energy ‘sheds load’’ that provides more details…
Multiple market notices for unplanned outages in Northern/Central NSW yesterday:
– MN117313 at 05:41: unplanned outage of Lismore – Coffs 330 kV at 0511, influencing constraints on Directlink
And then after load shedding (from 18:17):
– MN117323 at 19:41: unplanned outage of all 3 cables of Directlink at 18:45 (- but it looks like flow was restored by the next DI)
– MN117325 at 20:01: unplanned outage of Eraring – Newcastle 330 kV at 19:40
Speculation: some correlated transmission failures around Lismore, with load shedding in that sort of area and limited impact on overall NSW prices or supply/demand balance.
An article on RenewEconomy “Load shedding in NSW holiday spot after multiple transmission line trips” adds some more details.