A quick look at Dispatch Error for each individual Coal Unit (at 03:05 on Thursday 2nd April 2026)

For today (Thursday 2nd April 2026) we’ve already noted:

Part 1)  the ‘(Close to) Full Load trip of Kogan Creek early on Thursday 2nd April 2026’, which showed:

(a)  the trip is visible in the 03:05 Dispatch Interval (NEM time) … remembering the building blocks of time;

(b)  with a Dispatch Error for the KPP_1 unit being +720MW … remembering:

i.  that a positive dispatch Dispatch Error represents underperformance, relative to Target

ii.  so acting to drag the frequency down…

Part 2)  … which we saw in this ‘first look at the frequency performance, with today’s trip at Kogan Creek’.

… noting that the trip occurred at 02:59:54.4 … :

(a) But too late to be registered for the FinalMW snapshot for KPP1 for 03:00, and (as such):

(b)  The 03:05 dispatch interval shows (via FinalMW) both:

i.  The effect of the trip; but also

ii.  The corrective responses of many units;

Part 3)  We have also noted peeled the first layer of ‘What helped (and what didn’t help) to contain the frequency drop with this morning’s Kogan trip?’

… noting that:

(a)  In aggregate terms, Batteries, (other) Coal units, Hydro and Gas all helped to support the frequency;

(b)  But Wind Farms in aggregate did not help.

 

In this short (Part 4) follow-on article, we present this single chart of the single dispatch interval (03:05 NEM time) for all of the operational coal units:

2026-04-02-at-03-05-DispatchError-CoalUnits

From this chart, three quick observations:

1)  The positive Dispatch Error for the KPP_1 unit (at +720MW) dwarfs the other individual responses

… which is understandable

2)  Most other operational coal units provided support via negative Dispatch Error

… several as large as ~-20MW

3)  But there’s a curiosity about a couple units still having positive Dispatch Error

… something to explore if time permits to peel another layer…


About the Author

Paul McArdle
Paul was one of the founders of Global-Roam in February 2000. He is currently the CEO of the company and the principal author of WattClarity. Writing for WattClarity has become a natural extension of his work in understanding the electricity market, enabling him to lead the team in developing better software for clients. Before co-founding the company, Paul worked as a Mechanical Engineer for the Queensland Electricity Commission in the early 1990s. He also gained international experience in Japan, the United States, Canada, the UK, and Argentina as part of his ES Cornwall Memorial Scholarship.