Last Monday’s spot price volatility in New South Wales has prompted gigatokens’ worth of analysis on social and mainstream media. There are visualisations, walls of numbers and any number of human and AI-assisted commentaries out there for consumption. Outages, demand levels, cloud cover, windiness, transmission limitations, constraints, even “hog cycles” – they’ve all been picked over quite extensively.
This post aims to cut through all these to the proximate cause – what actions or decisions on the day led to – or, taken differently, could have avoided – that volatility?
That boils down pretty simply to how those high prices were set, and how the relevant spot market participants bid during the volatile period. As useful background, before speaking about how NSW divided into two, readers might like to refer to this ‘1st pass through, inspecting Supply-Side contributions in NSW on Monday 12th October 2026’.
Location, location, location
What does “relevant spot market participants” mean? In this case, it’s those who had available supply capacity, that was physically able to be dispatched, and who offered enough of that capacity at very high offer prices such that in aggregate, a slice of that high-priced capacity was still needed to balance supply and demand.
We start by breaking available New South Wales supply into two chunks, according to whether that supply was on the “wrong” or “right” side of the transmission constraint caused by an outage of Line 6 (Canberra – Capital) in southern NSW. That outage put a hard limit on the maximum power transfer from generation south and west of the constraint (including interconnector flow from Victoria) into the greater Sydney zone. Geographically, the affected NSW generators can be seen in this screenshot from ez2view:
Here’s how this generation was bid and dispatched in the first high-priced interval, 14:20 NEM time, when the spot price jumped to $23,107/MWh.
The highlighted values show that 4,001 MW of available capacity from this group of generators was offered at prices at or below $0/MWh (nearly all of it at the market floor price of -$1,000/MWh), but the aggregate dispatch target volume was over 1,100 MW less – almost all of that difference being curtailment due to the Line 6 outage.
Even if the few generators and batteries in this group offering at high prices had instead rebid their volumes to the price floor, it would have made no difference to the NSW spot price – no additional generation was able to get through the Line 6 constraint.
The right side of the constraint
It was only supply on the “right” side of this limitation that was in play for setting the spot price as demand in NSW grew. How was this supply offered to the market?
I’ve subdivided this right-side generation into VRE (wind and solar) and fully dispatchable (thermal, hydro and batteries) categories. Here’s how the VRE offered:
Very simple in this case – all the available 709 MW was offered at or below $0/MWh, and it was fully dispatched.
Note that 709 MW is a lot less than the nominal 4,035 MW maximum capacity of this subset of the wind and solar fleet – that’s mostly because it was cloudy and wind speeds were low. Not something those generators or anyone else could do anything about on this particular day.
The relevant parties
What about the remaining fully dispatchable generators available on the day and on the right side of the Line 6 constraint? Here’s how they bid at the 14:20 interval:
This shows the simple, proximate cause of the spot price jumping to $23,107/MWh (set by a discharge offer from Origin Energy’s Eraring battery): of the 7,877 MW available generation in this sub-grouping, 3,158 MW (40%) was offered at prices above $5,000/MWh (in fact the lowest offer price in the red band was over $20,000/MWh), and a slice of this high-priced capacity had to be dispatched to balance supply and demand.
A caveat here – not all of these “available” generation offers above $20,000/MWh could have been dispatched in just one interval. There are startup times for offline fast-start units like EnergyAustralia’s Tallawarra B and Snowy’s Colongra plant, as well as ramp-rate limits on units already online, especially coal-fired plant. But
- Less than 200 MW of high-priced capacity was actually required in this interval,
- Capacity at units already online or batteries (AGL’s Bayswater units or its Liddell battery, EnergyAustralia’s Tallawarra A, Sev.en’s Vales Point B or Origin Energy’s Eraring unit 4) could have been offered at lower prices through earlier rebids,
- Fast start plant operators could have had some of those units started up and offered at lower prices in advance, and
- Not even included here, Akaysha’s 700 MW Waratah battery had offered no discharge capacity to the market in this interval, although it did so a few intervals later.
Data, not opinion
None of the findings above means that the relevant participants should have done anything different from how they chose to offer their supply capacity on the day. There are almost certainly no breaches of market rules or guidelines here – and subject to those rules and guidelines, how participants choose to offer their capacity to the market is primarily a commercial decision. The intention – or perhaps hope – underlying the NEM’s spot market dispatch and pricing arrangements it that competition and risk management decisions will drive outcomes towards “efficiency”, however that’s defined.
The purpose of this post isn’t to dive further into these commercial or market design considerations, but to simply highlight that while dozens of the well picked-over factors I mentioned earlier can set up preconditions for price volatility, it’s ultimately (or is that proximally??) how participants choose to bid that almost always determines whether that volatility actually eventuates. On this particular day, it wouldn’t have required a major change in those choices for this post – and dozens of others – not to have been written.
=================================================================================================
About our Guest Author
![]() |
Allan O’Neil has worked in Australia’s wholesale energy markets since their creation in the mid-1990’s, in trading, risk management, forecasting and analytical roles with major NEM electricity and gas retail and generation companies.
He is now an independent energy markets consultant, working with clients on projects across a spectrum of wholesale, retail, electricity and gas issues. You can view Allan’s LinkedIn profile here. Allan will be occasionally reviewing market events here on WattClarity Allan has also begun providing an on-site educational service covering how spot prices are set in the NEM, and other important aspects of the physical electricity market – further details here. |






Be the first to comment on "The proximate cause"