A quick look (with ‘next day public’ data) at the (apparent) machinations at Millmerran unit 2 on Friday morning 9th October 2026

Yesterday we wrote ‘Other curious events occurred in QLD on Friday morning 9th October 2026 ( QLD Demand, and Millmerran 2)’ – and it’s useful to note that one reader (Andy James) commented quickly that day that:

‘One does not simply restart a coal unit at close to 100% MCR with the space of minutes after a full load trip. Suggests a SCADA issue. The apparent increase in system frequency supports this.’

 

So, as alluded to in yesterday’s article, today we take advantage of the ‘next day public’ data to look back at the 08:10, 08:15 and 08:20 dispatch intervals on Friday 9th October 2026, to see what else there is to see.

We use the ‘Unit Dashboard’ widget in ez2view to do this, with the table focused back on those 3 x dispatch intervals of interest:

2026-10-10-at-09-20-ez2view-UnitDashboard-MPP2

From this additional data we see:

1)  Firstly, the three dispatch intervals in question show the ‘End of Interval Power’ (or FinalMW) appearing to cycle

2)  Understanding this first step into the complexities of a Dispatch Interval, we can see how this data (even if spurious) feeds into the NEMDE dispatch process, meaning a Target of only 15MW for 08:15 and 08:20

… i.e. NEMDE assumes the unit is off, and uses the ROCUP rate of 3MW per minute to set the maximum ramp up to be only 15MW.

3)  Whilst the 08:15 dispatch also sees FinalMW at 0MW (i.e. suspiciously spurious)

(a)  The Dispatch Error of 15MW arrives because the FInalMW is again 0MW

(b)  Hence Conformance Status automatically assessed as ‘Off-Target’

4)  Whereas in the 08:20 dispatch interval, it appears that the SCADA data resumes correctly:

(a)  So, whilst the Target is only 15MW (again)

(b)  The FinalMW magically re-appears to be 435MW

(c)  Meaning a Dispatch Error of –420MW (i.e. way above Target)

(d)  Hence Conformance Status automatically assessed as ‘Off-Target’ again

 

So, all in all, Andy James’ assumption (of a SCADA issue) seems to be the most logical explanation.

 

Incidentally (or coincidentally?), about an hour later that morning we noticed other issues with data delivery at the AEMO (and updated our Service Status page here to suit).  I wonder if this is not part of the same series of issues AEMO was experiencing?


About the Author

Paul McArdle
Paul was one of the founders of Global-Roam in February 2000. He is currently the CEO of the company and the principal author of WattClarity. Writing for WattClarity has become a natural extension of his work in understanding the electricity market, enabling him to lead the team in developing better software for clients. Before co-founding the company, Paul worked as a Mechanical Engineer for the Queensland Electricity Commission in the early 1990s. He also gained international experience in Japan, the United States, Canada, the UK, and Argentina as part of his ES Cornwall Memorial Scholarship.

Be the first to comment on "A quick look (with ‘next day public’ data) at the (apparent) machinations at Millmerran unit 2 on Friday morning 9th October 2026"

Leave a comment

Your email address will not be published.


*